The 90 minute ASHRAE Technical Committee
TC 5.10 seminar covered a variety of CKV areas. This seminar
is available from ASHRAE on DVD or full line access. See
the ordering details at the end of this section.
Speakers made many excellent points that HVAC designers
need to consider when developing plans and specifications
for a new installation. The speakers often made similar points
regarding the use of UL 710 listed hoods, kitchen comfort
and energy savings available to owners and operators.
Many good questions were posed by audience members after
each of the speakers made their presentations. We have included
email addresses for each of the speakers should you wish
to contact them.
Steve Brown of LC-Systems was
the first speaker and gave his ideas for “Dehumidification
Strategies”. Noteworthy is the fact that the proper
hood choice can reduce air requirements by up to 30%. He
pointed out the need to deliver make up air as far away from
the hood as possible with displacement air as an alternate
choice. He discussed tempering make up air which other speakers
also encouraged in their presentations.
A major consideration he suggested is to minimize the impact
of space humidity which leads to slippery floors. Steve stated
that 51% of kitchen accidents are directly related to slippery
floors and that 59% of construction claims are directly related
to moisture and humidity claims. Contact Steve at: stevebrown@lc-systems.com.
Doug Horton of D.J.Horton & Associates presented
an explanation of the “Impacts of Low Heating and Cooling
Balance Points”. His research has shown that in many
instances when examining roof top systems, both heating and
cooling systems are in operation at the same time. In the
majority of installations, no one is aware that both systems
are operating simultaneously and wasting valuable energy.
Contact Doug at: djhorton64@attbi.com.
Mark Finck , from Burger King’s
Support Center discussed “Exhaust Duct Cleaning
Experiences” from a users’ viewpoint. He talked
about the lack of effective grease capture by current filters
as a big concern leading to many duct and fan problems.
(Watch for an UP YOUR STACK™ New Technologies article
next month featuring dual filter stage technology with
significantly improved capture abilities.)
The lack of professionalism within the duct cleaning industry
was also discussed by Mark. He discussed the need for a more
reasonable method of determining when to clean ducts based
on need, not just meeting a pre-determined schedule. See
the UP YOUR STACK™ Newsletter article entitled “FIRE
SAFETY-Restaurant Duct Cleaning! What do Operators Get for
their Buck?” at the following link: http://www.upyourstack.com/newsletters/112404/FireSafety.asp.
Mark also talked about using round ducting to reduce grease
deposits on the side walls of the duct as well as lowering
velocity to an average of 900 FPM based on Burger King’s
needs. Contact Mark at: mfinck@whopper.com.
J. Carlos Haiad, P.E. of Southern
California Edison made the case for “Demand
Ventilation Applications”. He pointed out that the
new NFPA lower threshold of exhaust air allowed for the
use of variable speed controls. Such a system allows the
fans to operate at lower speeds when little or no cooking
is underway.
Operating at lower speeds during slow cooking times can
have significant energy savings for the owner and operator.
Paybacks examples vary depending on utility rates. Examples
ranged from 13 months to two years.
These systems are relatively easy to install as retrofits
and very simple when designing a new hood system. The systems
should always interlock and control both the exhaust and
make up air fan units.
Carlos noted that the low end of 500 FPM exhaust is only
meant for an idle or no cooking period. Higher speeds are
progressively employed as the cooking process begins at various
points along the cooking lineup. It was pointed out that
the previous average of designing systems between 1500-2100
FPM is being successfully reduced by hundreds of CFM using
demand ventilation technology. Contact Carlos at: carlos.haiad@sce.com.
Finally, John Clark, P.E. of Hammel,
Green and Abrahamson, Inc., presented a list of “The
Terrible Two’s”. His often humorous discussion
included reasons the kitchen is too hot, too cold, too
drafty, too smoky, too expensive, too noisy and too complicated.
Key recommendations included using UL710 listed equipment
for maximum efficiency and air conditioning the kitchen
for employee comfort and retention.
John strongly advised when designing the make up air system,
that make up air be tempered and that 10-20% of transfer
air from the dining space be used to control odors.
Other points included the use of side curtains to reduce
smoke problems caused by side drafts and removal of four
way ceiling diffusers anywhere within 12’-0” of
the hood. Three way diffusers with the blank side facing
the hood or slot diffusers that spread out the make up air
are acceptable.
John also pointed out the need to interlock the exhaust
fan and replacement air systems as did most every other speaker.
A final point was his call for pressure testing of welded
exhaust duct systems noting that experienced welders averaged
a minimum of three attempts to close all the leaks discovered
in what otherwise were assumed to be completely welded duct
seams. Contact John at: JClark@hga.com.
ASHRAE is making Audio Recordings with PowerPoint’s
from this seminar and approximately 50 other seminars available
online at $149. ASHRAE members can purchase access at $99.
DVD’s are also available at $199 or $149 to ASHARE
members plus shipping. You can purchase directly from UP
YOUR STACK™.com. Please email us at info@upyourstack.com if
interested. Available during March.
For your convenience, the company store will be available
within sixty days to allow online ordering of all Codes & Standards
documents directly from our website.
|