Upon
reading the new Chicago mechanical code sections dealing
with grease ducts and hoods, we were immediately struck by
some serious omissions. While Chicago’s Mayor Daley
had wished to adopt model ICC Code language, Chicago’s
new mechanical code language fails to include certain elements
critical to energy conservation.
City code writers did not include model code language developed
through years of extensive research and testing by UL, the
University of Minnesota, ASHRAE and both private and industry
test labs.
By not following the mayor’s instructions, Chicago
code writers created a new mechanical code that is out of
step with the commercial kitchen ventilation (CKV) industry.
LISTED HOODS
By leaving out any reference to listed hoods, UL listed
hoods are not available as an option. Listed hoods are the
main choice of savvy CKV designers, building owners and operators
for their energy savings.
- The new city mechanical code contains no reference to
the use of listed hoods. The Q formulas given in the new
code reflect the use of outdated and oversized methods
of dealing with kitchen ventilation. These formulas are
only used with non-listed commercial kitchen hoods.
A. Listed hoods are those that are certified by UL
and others to operate at significantly lower air quantities
to that of the old Q or square foot formulas. This
listed hood option reflects in energy savings and operating
costs to the building owner or operator.
B. Lower air
quantities are available to designers using listed
hoods and allow both smaller ducts and duct shafts,
a major cost savings to owners and developers.
C. The elimination
of listed hoods quietly accepts the fact that poorly
constructed hoods may be acceptable to city inspectors.
Safety may often be compromised since many are fabricated
substandard. These hoods are built only for price
and may not follow nationally recognized standards
for safety. These compromises can be subtle and are
often missed by city inspectors who are unable to recognize
the differences.
D. Item C will be welcomed by general
contractors who often regard kitchen hoods as a place
to hide higher profit by ignoring well designed hoods
in favor of inexpensive built for a price models.
LOWER AIR VELOCITY
A second instance of ignoring changing codes and standards
is the failure to include the use of new lower air velocity
industry research, University of Minnesota research project
number 1033-RP, funded by ASHRAE.
- The limiting high air duct
velocity of 1500 to 2100 FPM (feet per minute) through
the grease duct is retained in the Chicago July 28, 2004
Mechanical Code. It applies to non-listed and listed hoods.
See item 2 and the IMPORTANT DISTINCTION box below.
- The
current NFPA Standard No. 96-2004 (National Fire Protection
Standard) has lowered the base figure to 500 FPM. The
ICC in their International Mechanical Code has also adopted
this lower base air velocity. ICC Proposal M45-03/04
was approved in September 2003. The revision appears in
the 2004 Supplement. It will appear in the next published
hard cover edition in 2006.
| IMPORTANT
DISTINCTION – Designers
will continue to use the 1500-2100 FPM design criteria.
The new lower 500 FPM enables the option of including
variable speed fan technology. A variable speed fan will
include the use of sensors that lower fan speed during
idle or slow cooking times. These sensors recognize the
absence of cooking effluents rising off the cooking surfaces
in slow and idle periods, allowing the fan to operate
at a slower speed. As cooking begins and effluents enter
the air stream, the sensors automatically adjust the
fan speed upward. |
ENERGY CONSERVATION
Energy conservation is the primary consideration. Testing
sponsored by ASHRAE at the University of Minnesota has proven
the practicality of this new reduced base figure, allowing
the lower 500 FPM air velocity to be adopted using variable
speed technology. The benefits are as follows:
A. Lower energy costs for the lifetime of a given installation
are immediately available to the owners of buildings for
as long as they are in use. Estimates of savings vary from
$1.00 to 3.00 per cubic foot of annual air costs. That
includes the cost of heating and air conditioning a building
via make-up air to replace the contaminated air exhausted
by the hood(s).
B. Variable speed fan and control technology
becomes the key to using fans that automatically adjust
to the cooking effluent load at any given time, allowing
further annual air operating costs.
C. Duct systems and building duct shafts using listed
hoods are generally smaller reducing the cost of construction
to owners and keeping a lid on ever rising per square foot
costs.
D. KEY POINT -The lower FPM air threshold provides
the allowance of potentially using existing CKV duct
systems and building air shafts when remodeling - a major
consideration with as many restaurants as Chicago has.
Much of the progress made by CKV industry members over
the last several years goes unrecognized by these omissions
in the new Chicago Mechanical Code.
WHY?
We have learned that there may be some relief being developed
in the way of an addendum or revisions. However, at this
time we are unaware of the details. UP
YOUR STACK™ has
offered to assist the committee in correcting these issues.
It remains for the City Council to vote on the changes. A
vote is not anticipated until some time in 2005.
There is no indication that the lower air velocity allowing
variable speed fan technology is being considered at this
time. We encourage the committee to recognize and add this
technology and code language.
What happens in the interim? Chicago officials maintain
they can only respond to what is written in the code. Exactly
what does that mean?
HIGHER CONSTRUCTION & ENERGY COSTS
The City Council passed the new code on July 9, 2004.
That means that since July 28, 2004, when the new Chicago
Municipal Building Code was issued, listed hoods are neither
acceptable, nor recognized in the city. It may be confusing
enough for private restaurant operators who are accustomed
to co-existing with the cities code inspectors and code language,
but chains are another story entirely.
National chains, and Chicago has them all, rely on good
choices for their equipment and design. When the choice to
use a listed CKV hood is taken away without any apparent
reason, chains are forced to deal with many decisions. Greater
CFM needs create the primary reason resulting in larger exhaust
ducts, larger exhaust fans, larger heating and air conditioning
systems. These choices result in higher construction costs
and higher energy costs for the life of the system.
We believe that creates an unwelcome sign by the City of
Chicago.
When will this situation be rectified by the City Council?
The council holds the power to make the changes and include
listed hoods. The key question becomes when?
WHAT HAPPENS NOW?
What happens in the interim? Architects, mechanical engineers,
developers, owners, designers, consultants and suppliers
are left with a decision. How should they respond to the
code as written?
Should they redesign at higher costs to all?
Should they delay designs and construction pending City
Council action?
ACTION CALL
Clearly neither of the above becomes a good option. We
suggest writing to the mayor at his office. If enough concern
is shown, we hope the city will respond in a timely manner.
The mayor and related department heads can be reached at
the following address.
Mayor Richard J. Daley
Office of the Mayor
121 N. LaSalle St. Room 507
Chicago , IL 60602
Cc: Mr. Fabio Grego,
Department of Construction and Permits
Mr.
Stan Kaderbeck, Building Commissioner
Mr. Tom Domain, Ventilation
Section Chief
The Chairman, for the Mechanical Code Working Group coordinating
city efforts is:
Mr. Anthony B. McGuire, P.E.
President
McGuire Engineers
300 S. Riverside Plaza
Chicago , IL 60606