Type I hoods come in numerous styles
and various categories. All model codes use the Type I and
Type II terms. A Type II hood is not meant for grease removal
and is only used to remove steam, vapor or heat. Type II hoods typically do
not include a fire suppression system unless the ductwork merges with a Type
I duct system. When in doubt, contact your local AHJ for their approval as
to use and fire suppression requirements. Never specify a Type II hood when
grease will be present. You may however, use a Type I hood in lieu of a Type
II hood.
Type I hoods include listed grease filters and fire suppression
equipment. Baffles or extractors may replace filters when
tested and listed for such use by a certification agency.
We talked about the advantages of a listed hood vs. a non-listed
version in our November Newsletter. We will concentrate on
listed hoods here. To obtain a listing, manufacturers must
submit hood models for evaluation by UL to meet Standard
710, the “Standard for Safety for Exhaust Hoods for
Commercial Cooking Equipment”.
BASIC CATEGORIES
There are two basic categories spelled out in UL 710, hoods
with dampers and those without dampers. When a model with
a fire actuated damper is selected, the damper is usually
located at the exhaust duct opening and closes when fire
is detected. This action prevents flames from entering the
duct system and traveling up to the roof. If the hood has
an internal duct opening for makeup air, it will normally
include a damper as well. Fire actuated dampers when used,
are an integral part of a listed device. If you have any
questions about what is acceptable, refer to the local building
department or fire inspectors for applicable codes in the
project area when making a decision.
Listed exhaust hoods with fire-actuated water systems are
typically water-wash hoods in which the wash system also
operates as a fire extinguishing system. In addition to meeting
UL 710, hoods are tested under UL 300, the “Standard
for Safety For Fire Testing of Fire Extinguishing Systems
for Protection of Restaurant Cooking Areas”.
STYLES
Now for the various types or styles of Type I hoods. There
are six versions and these are industry accepted ASHRAE descriptions:
Wall Mounted - Often referred to as a canopy hood
Single
Island - Referred to as a canopy hood over a single line
of equipment
Double Island - Same as above with back to
back cooking lines
Backshelf - Only used for counter
level equipment and has a lower profile
Eyebrow - Smaller
configuration mounted to ovens and dishwashers
Pass-Over
- Used with counter level equipment and used to serve plates
over
to the serving side (May have exhaust ducts to side
or employ
a downdraft configuration.)
Recirulating - Cleans grease
laden air within itself, releasing air back within the building
space. (See explanation below).
Ultraviolet - Refers to the
UV light system and can fit into several of the hood categories
above. (See explanation below).
ACGIH or the American Conference
of Governmental Industrial Hygienists in their 2001 edition
titled Industrial Ventilation use different terms to describe
hood types. These terms are not generally used by kitchen
equipment professionals but may be used by some environmental
health departments. We list them here in the event you
encounter one of these terms:
HAW - Hood against wall
ITH - Island type hood
LSW - Low side wall
Reciruclating hoods exist in their own separate category.
The recirculating system is listed under UL Subject 710B.
This type of hood may also be referred to as a ductless hood
since there is no duct to the roof. Ducts may extend to another
room or area for discharge of the cleaned air. Also refer
to NFPA 96, Chapter 10. Recirulating hoods are for use only
with electric equipment. Recirculating hoods are not for
use with gas fired or solid fuel equipment. Capacities are
limited. Designers should work with factory representatives
to determine effective capacities for given situations.
Ultraviolet hoods refer to the ultraviolet light system
generally located directly behind the listed filters. Ultraviolet
light chemically reacts with grease particles suspended in
the air stream and changes the chemical composition from
grease molecules to carbon dioxide and a limited amount of
water vapor. The ultraviolet light is able to extract small
particles under 2 microns, something most filters have difficulty
with. More of these systems are being installed recently
with the frequency of duct cleaning being reduced. While
numerous systems are installed in the United States and Canada,
the area around Vancouver, BC has seen many of these successfully
installed within the last few years. Note that ultraviolet
light may also be part of pollution control devices downstream
of the exhaust fan.
BENEFITS
Remember that a listed hood can save an owner thousands
of dollars over the life of a system by operating with less
exhaust and make up air than an unlisted device. Choosing
a hood is more than picking the least expensive hood that
fits over a given cooking lineup. It deserves consideration
in terms of choosing a model that fits the need of the cooking
lineup, proper overhangs and air flow requirements. It is
the amount of airflow required that will impact the cost
to an owner over the lifetime of the installation.
ASHRAE HANDBOOK
The most informative resource for all designers is the
2003 ASHRAE HANDBOOK, Chapter 31, titled Kitchen Ventilation.
You can order this handbook directly from UP YOUR STACK™ by
sending us an email at info@upyourstack.com.
Our on-line store will be open in early 2005. Watch for the
announcement.
The December 2004 Journal of Environmental Health features
an article titled Kitchen Hood Performance in Food Service
Operations. The study examined hood flow rates in 60 restaurants
and a total of 89 hoods. Only 24 percent met ASHRAE guidelines
for adequate air flow. This study also deals with cleanliness
and sanitarians’ inspection reports. A link was not
available at the time of this newsletter release.
Ref: 2003 ASHRAE Handbook |